Description
The measuring of CO2 is based on the principle of infrared radiation attenuation dependence on the CO2 concentration in the air (NDIR). Built-in auto-calibration function ensures very good long term stability.
Measurement of the relative humidity is based on the principle of capacitive polymer sensor. The sensor has built-in two separate analog outputs – one for the actual concentration of CO2 and the other for the current relative humidity. If the sensor contains 2 relays can be set two switching modes: standard (always one relay switched according to one quantity), a cascade mode (according to a selected quantity switch two relays with different levels of switching). Cascade switching, for example, can be used to switch power air conditioning units. The two rotary switches can be independently set the level at which the corresponding relay switches.
Sensor can efficiently manage ventilation and heat recovery units, based on current air quality. By three LED indicators can be easily checked the current air quality. Preferred eco level means good indoor air quality needed to achieve a sense of well-being and at the same time can reduce energy costs for heating or air conditioning. Based on these measurements can be directly controlled ventilation, air conditioning and heat recovery units in an efficient manner
Parameter | Value | |
Supply voltage range | 14 V – 40 V DC or 18 V – 30 V AC | |
Average consumption | 0,5 | W |
Ingress protection | IP20 | |
CO2 measuring range | 0 – 2000 | ppm |
CO2 accuracy | ± 35 ppm + ±5 % of reading | |
CO2 relay – hysteresis | 100 | ppm |
CO2 rate rise | max 1 | min |
CO2 step response | (90 %) 80 | s |
RH measuring range | 0 – 100 % | RH |
RH accuracy 20 – 80 % | ± 3 % | RH |
RH accuracy 0 – 100 % | ± 6 % | RH |
RH switching hysteresis | 5 % | RH |
Max. switching voltage | 250/30 | V AC / V DC |
Max. switching current | 5/5 | A AC /A DC |
Working humidity non condensing | 0 – 95 % | RH |
Working temperature no condensing | 0 to +50 | °C |
Storage temperature | -20 to +60 | °C |
Expected lifetime | min. 10 | years |
Dimensions | 90x80x31 | mm |
Attached documents