Description
Built-in advanced iVOC sensor is sensitive to volatile organic substances typically contained in the stuffy air – gaseous metabolic products of human bodies and other gaseous pollutants such as formaldehyde, cooking vapors, fumes from paints, varnishes, adhesives, detergents, etc. that CO2 sensor does not detect. NL-iVOC sensor detects gaseous pollutant substances in the air that are the main reason for ventilation. Sensor NL-iVOC approximates to human perception of air quality. The output of the sensor is calibrated as equivalent to a standard CO2 sensor.
Measurement of the relative humidity is based on the principle of capacitive polymer sensor.
The sensor has built-in two separate analog outputs – one for the actual concentration of VOC and the other for the current relative humidity. Sensor also contains one relay. Relay´s response – VOC or RH can be set by shorting jumper. Level of air quality at which the relay switches can be easily adjusted by the rotary switch. Current air quality can be easily checked the by three LED indicators. Eco level means good indoor air quality needed to achieve a sense of well-being together with optimizing energy costs for heating or air conditioning.
Parameter | Value | |
Supply voltage range | 14 V – 40 V DC or 18 V – 30 V AC | |
Average consumption | 0,5 | W |
Ingress protection | IP20 | |
iVOC* measuring range | 450 – 2000 | ppm |
iVOC* relay – hysteresis | 100 | ppm |
RH measuring range | 0 – 100 % | RH |
RH accuracy 20 – 80 % | ± 3 % | RH |
RH accuracy 0 – 100 % | ± 6 % | RH |
RH switching hysteresis | 5 % | RH |
Max. switching voltage | 250/30 | V AC / V DC |
Max. switching current | 5/5 | A AC /A DC |
Working humidity no condensing | 5 – 95 % | RH |
Working temperature | 0 to +50 | °C |
Storage temperature | -20 to +50 | °C |
Expected lifetime | min. 10 | years |
Dimensions | 90x80x31 | mm |
Attached documents
ds_NL_IVOC_en_V4_1503203_2.pdf
um_NL_IVOC_en_V3_1503201_2.pdf