NL iVOC-RH-R sensor

Room sensor NL-iVOC+RH-R is used to monitor air quality inside buildings and power control ventilation (HVAC) systems according to current levels of air pollution. The sensor measures the concentration of gaseous organic substances in the air (VOC) and relative humidity (RH) in air. The sensor can be effectively used in offices, classrooms, restaurants, kitchens, fitness centrums, commercial facilities etc.

  • measures VOC and RH
  • close to the human perception of odors
  • compatibility with CO2 standard
  • 2x analog voltage/current output
  • 2x output relay – 2x NO/C
  • cascade switching
Category:

Description

Built-in advanced iVOC sensor is sensitive to volatile organic substances typically contained in the stuffy air – gaseous metabolic products of human bodies and other gaseous pollutants such as formaldehyde, cooking vapors, fumes from paints, varnishes, adhesives, detergents, etc. that CO2 sensor does not detect. NL-iVOC sensor detects gaseous pollutant substances in the air that are the main reason for ventilation. Sensor NL-iVOC approximates to human perception of air quality. The output of the sensor is calibrated as equivalent to a standard CO2 sensor.

Measurement of the relative humidity is based on the principle of capacitive polymer sensor.

The sensor has built-in two separate analog outputs – one for the actual concentration of VOC and the other for the current relative humidity. Sensor also contains one relay. Relay´s response – VOC or RH can be set by shorting jumper. Level of air quality at which the relay switches can be easily adjusted by the rotary switch. Current air quality can be easily checked the by three LED indicators. Eco level means good indoor air quality needed to achieve a sense of well-being together with optimizing energy costs for heating or air conditioning.

ParameterValue 
Supply voltage range14 V – 40 V DC or 18 V – 30 V AC
Average consumption0,5W
Ingress protectionIP20
iVOC* measuring range450 – 2000ppm
iVOC* relay – hysteresis100ppm
RH measuring range0 – 100 %RH
RH accuracy 20 – 80 %± 3 %RH
RH accuracy 0 – 100 %± 6 %RH
RH switching hysteresis5 %RH
Max. switching voltage250/30V AC / V DC
Max. switching current5/5A AC /A DC
Working humidity no condensing5 – 95 %RH
Working temperature0 to +50°C
Storage temperature-20 to +50°C
Expected lifetimemin. 10years
Dimensions90x80x31mm

 

Attached documents

ds_NL_IVOC_en_V4_1503203_2.pdf
um_NL_IVOC_en_V3_1503201_2.pdf