ADS-CO2-D duct sensor

The sensor is used to measure the amount of CO2 in an air duct. It suits for air quality control systems, ventilation and heat recovery systems.

    • works on the optical NDIR principle
    • doesn’t need maintenance during operation
    • 0 – 10V analog output
    • adjustable sensitivity
    • long service life and stability

Description

Sensor is equipped with voltage/current analog output and with an output relay. The analog output value is proportional to the concentration of CO2. The measuring of CO2 works on the principle of infrared radiation attenuation dependence on the CO2 concentration in the air. Built-in electronics converts the infrared radiation attenuation changes in the measuring cell to the analog output. The sensor is capable to measure the CO2 in the air concentration in the range of 370 up to 2000 ppm.

ParameterValueUnit
Power supply optional –14 – 40V DC
18 – 30V AC
Power consumption50mA
Voltage output0 – 10V DC
Current output 10 – 20mA
Current output 24 – 20mA
Switched voltagemax 250V AC
Switched currentmax 3A
Measuring range370 – 2000ppm
Resolution1ppm
Accuracy± 45ppm ± 5%ppm
Working temperature0 to +40°C
Working humidity5 to 95%RH
Storage temperature-30 to +70°C
Expected lifetimemin. 10years
Dimensions257x100x60mm
– Warm-up: operational after 1 minute since power on.

– The declared accuracy is reached after 4 days of continuous power supply.

– Calibration during operation is not necessary.